8004 series Power line filters for shielded cabinet

This series of power line filters are specially designed for well grounded shielded cabinet with rated voltage of 250VAC/50-60Hz. It is compact and in compliance with class B and C standards for shielded Cabinet.

The 8004 series Power line filters for shielded cabinets is a superior filter housed in a two compartment casing that achieves 100 dB insertion transmission loss at 14 kHz till 40 GHz.The circuit is designed as a double- circuit with high quality rod cores providing inductanace. These cores do not saturate due to their large air gap and they are insensitive to asymmetrical load.

This series of power line filters is specially designed for well grounded shielded cabinet with rated voltage of 250VAC/50-60Hz. It is compact and in compliance with Class B and C standards for shielded cabinet. The 8004 series is particulary suitibel to be used on MRI rooms.

This series is only offered as a two line filter (phase and neutral).


Advantages

  • High attenuation level for lower frequencies
  • Suitable for use under extreme conditions (military applications)
  • Wear resistant
  • Insensitive for corrosion

Applications

  • Shielded rooms
  • Shielded chambers
  • Anechoic chmabers
  • Military applications
8004 series Power line filters for shielded cabinets
8004 series Power line filters for shielded cabinets

Product range

All power line filters mentioned above are intended to be placed before the earth leakage circuit breaker.
When you need a power line filter that you can place after the earth leakage circuit breaker,
you can use the LL version (8004-16-LL).

* These filters are available upon request.
Type IR (A) I Leakage (mA) * Outline drawing Shielding Effectiveness (dB)
8004-2-6 2×6 30 1 100dB, 14k-40GHz
8004-2-16 2×16 30 1
8004-2-20 2×20 30 1
8004-2-32 2×32 30 2
*8004-2-16-LL 2x16 3 1 See graph below
or
download technical datasheet
*8004-2-16-EP 2x16 <3 1  See graph below
or
download technical datasheet

*If voltage between neutral and earth is 0V


Shielding performance

8004-2-16-LL shielding performance graph
8004-2-16-LL shielding performance graph
8004-2-16-EP shielding performance graph
8004-2-16-EP shielding performance graph. This version has a better shielding performance compared to the 8004-2-16-LL version and has the same low leakage (3mA)

Dimensional diagrams

Diagram 1
Diagram 1
Diagram 2
Diagram 2