Super high performance 2 power line filter

The super high performance 2 power line filter range is used for HEMP protection of power lines.


High performance:

  • HEMP small residual
  • high insertion loss
  • LEMP protection type 1

The general design corresponds with the attenuation request of shielded sites (Faraday cages, shelters...).

These protections can be used for the following single or three phase electrical networks:

  • 250 VAC - 50/60 Hz
  • 250/440 VAC - 50/60 Hz
  • 400 VDC
  • 5 to 800 A

Attenuation curves

Attenuation (50 Ω on load) MIL STD 220 B or GAM T21
These values are measured under laboratory conditions.
In your situation results may differ, please read our Guarantee.

Mounting

These protections are designed for mounting on the penetration panel or directy on the non-painted wall of the Faraday cage.

  • Feed-thr nozzle (supplied with filter) is used to ensure high frequency performance. A non-rotation system ensures correct and easy mounting.

Maximum torque value

M 5: 2.2 Nm
M 6: 2.45 Nm
M 8: 10 Nm
M 10: 15 Nm
M 12: 20 Nm
M 33 x 2: 40 Nm
M 60 x 2: 40 Nm
M 80 x 2: 40 Nm

General characteristics

The super high performance 2 protection range made from a metallique case painted RAL 7032 which provides an excellent earth bonding and electromagnetic shielding. The cabinet is seperated into three parts:

  • Network access (with arrsters).
  • Filtering area
  • Shielded area which has a metal penetration nozzle supplied with the filter.

The lids of the connection area are equipped with a high performance HF gasket.


Technical characteristics

Operating temperature : - 40°C + 50°C
for 800 A : - 40°C + 40°C
Storage temperature : - 40°C + 70°C
Test voltage : 1150 VDC
Overvoltage protection : special arrester ref: 8860-05
In (15 strokes) : 35 kA (8/20 μs)
Iimp (1 stroke) : 35 kA (10/350 μs)

HEMP characteristics:

Underwave 20/500 ns 4 kA + wave 50/150 μs 100 A residual < 6 A

For the explanation of the reference see chapter how to order belowConnectionFor the shielded area:Cables are passed through metallic nozzles ensuring that the RFI sealing between the inside of the cages and the shielded area is guaranteed. Connections are made by copper threaded terminals (Copper bars for 800 A). A connection for ground is available and can be used as an earth terminal.03366;">For the external area:
Cables exit via a grommet. Connections are made by copper threaded terminals. A connection for ground is available, either internally or externally, and can be used as an earth terminal. 
ReferenceNetworksMax.
Current
Rated voltage UR
(V rms)*
Max. ohmic
resistance
per line
Max. leakage
current
at 250V / 50 Hz
Approximative
weight
(A)-(mΩ)(A)(kg)
SHP2 - 2005Single phase 5 250 - 50/60 Hz 200 0,1 15
SHP2 - 3005Three phase 5 440 V - 50/60 Hz 200 0,1 18
SHP2 - 4005Three phase + N 5 250/440 V - 5-0/60 Hz 200 0.1 20
SHP2 - 2016Single phase 16 250 - 50/60 Hz 72 0.15 43
SHP2 - 3016Three phase   440 V - 50/60 Hz 72 0.15 50
SHP2 - 4016Three phase + N 16 250/440 V - 5-0/60 Hz 72 0.15 57
SHP2 - 2032Single phase 32 250 - 50/60 Hz 25 0.5 45
SHP2 - 3032Three phase 32 440 V - 50/60 Hz 25 0.5 52
SHP2 - 4032Three phase + N 32 250/440 V - 5-0/60 Hz 25 0.5 60
SHP2 - 2064Single phase 64 250 - 50/60 Hz 8 0.5 35
SHP2 - 3064Three phase 64 440 V - 50/60 Hz 8 0.5 60
SHP2 - 4064Three phase + N 64 250/440 V - 5-0/60 Hz 8 0.5 65
SHP2 - 2100Single phase 100 250 - 50/60 Hz 5 1 40
SHP2 - 3100Three phase 100 440 V - 50/60 Hz 5 1 65
SHP2 - 4100Three phase + N 100 250/440 V - 5-0/60 Hz 5 1 70
SHP2 - 2125Single phase 125 250 - 50/60 Hz 4 1 40
SHP2 - 3125Three phase 125 440 V - 50/60 Hz 4 1 65
SHP2 - 4125Three phase + N 125 250/440 V - 5-0/60 Hz 4 1 70
SHP2 - 2200Single phase 200 250 - 50/60 Hz 1.5 1.5 60
SHP2 - 3200Three phase 200 440 V - 50/60 Hz 1.5 1.5 85
SHP2 - 4200Three phase + N 200 250/440 V - 5-0/60 Hz 1.5 1.5 100
SHP2 -2300Single phase 300 250 - 50/60 Hz 1 4 80
SHP2 -3300Three phase 300 440 V - 50/60 Hz 1 4 110
SHP2 -4300Three phase + N 300 250/440 V - 5-0/60 Hz 1 4 135
SHP2 - 3800Three phase 800 440 V - 50/60 Hz 0.5 5 250
SHP2 - 4800Three phase + N 800 250/440 V - 5-0/60 Hz 0.5 5 300
These values are measured under laboratory conditions.
In your situation results may differ, please read our Guarantee.

For the explanation of the reference see chapter how to order below


Connection

For the shielded area:

Cables are passed through metallic nozzles ensuring that the RFI sealing between the inside of the cages and the shielded area is guaranteed. Connections are made by copper threaded terminals (Copper bars for 800 A). A connection for ground is available and can be used as an earth terminal.

For the external area:

Cables exit via a grommet. Connections are made by copper threaded terminals. A connection for ground is available, either internally or externally, and can be used as an earth terminal.


Dimensions in mm

Single phase

ReferenceABCDEFGHJKLCurrent
SHP2 - 2005 620 250 150 44 M 27 20 19 526 190 41 M 4 5 A
SHP2 - 2016 500 280 150 50 M 33 26 33 400 220 46 M 6 16 A
SHP2 - 2032 500 280 150 50 M 33 26 33 400 220 46 M 6 32 A
SHP2 - 2064 900 440 150 50 M 33 26 33 800 320 46 M 8 64 A
SHP2 - 2100 900 440 150 50 M 33 26 33 800 320 46 M 8 100 A
SHP2 - 2125 900 440 150 50 M 33 26 33 800 320 46 M 8 125 A
SHP2 - 2200 1110 400 230 75 M 60 50 52 965 300 80 M 8 200 A
SHP2 - 2300 1500 450 260 75 M 60 50 52 1325 370 80 M 12 300 A

* For the explanation of the reference see chapter how to order below

Three phase

ReferenceABCDEFGHJKLCurrent
SHP2 - 3005 720 250 150 44 M 27 20 19 626 190 41 M 4 5 A
SHP2 - 3016 580 400 150 50 M 33 26 33 480 340 46 M 6 16 A
SHP2 - 3032 580 400 150 50 M 33 26 33 480 340 46 M 6 32 A
SHP2 - 3064 1110 440 150 75 M 60 50 52 965 320 80 M 8 64 A
SHP2 - 3100 1110 440 150 50 M 33 26 33 800 320 46 M 8 100 A
SHP2 - 3125 1110 440 150 75 M 60 50 52 965 320 80 M 8 125 A
SHP2 - 3200 1110 600 230 75 M 60 50 52 965 500 80 M 8 200 A
SHP2 - 3300 1500 600 260 85 M 80 65 65 1315 520 100 M 12 300 A
SHP2 - 3800 1350 650 265 85 3 x M60 - 52 1165 550 100 - 800 A

* For the explanation of the reference see chapter " how to order " below

Three phase + N

ReferenceABCDEFGHJKLCurrent
SHP2 - 4005 720 250 150 44 M 27 20 19 626 190 41 M 4 5 A
SHP2 - 4016 580 500 150 50 M 33 26 33 480 440 46 M 6 16 A
SHP2 - 4032 500 280 150 50 M 33 26 33 400 220 46 M 6 32 A
SHP2 - 4064 1110 590 150 75 M 60 50 52 965 470 80 M 8 64 A
SHP2 - 4100 1110 590 150 75 M 60 50 52 965 470 80 M 8 100 A
SHP2 - 4125 1110 590 150 75 M 60 50 52 965 470 80 M 8 125 A
SHP2 - 4200 1110 800 230 75 M 60 50 52 965 660 80 M 8 200 A
SHP2 - 4300 1500 720 260 85 M 80 65 65 1315 620 100 M 12 300 A
SHP2 - 4800 1350 850 265 85 4 x M 60 - 52 1165 720 100 M 12 800 A

* For the explanation of the reference see chapter how to order below


How to order

The picture below explaines how to generate a Super high performance 2 part number.

    • Serie (SHP2 = Super high performance 2)
    • Smount of phases
    • Current (A)
    • Amount of volts (250/400)
How to order a Super high performace power line filter